The defaults voltage ranges for the PCD packs are as follows:

 

LampType

MlvMode

Voltage1Percent_Pcd

Voltage100Percent_Pcd

Fluorescent (1)

Disabled (1)

56 V (56)

110 V (110)

Incandescent (2)

Disabled (1)

24 V (24)

117 V (117)

MLV (3)

Enabled (2)

24 V (24)

117 V (117)

 