Follow

nCLASS: What Are The "nCLASS" Program Options For The nPODM 4S?

nCLASS has preset conditions for the nPODM 4S with the following scenes:

OPTION 1:

  • Button 1 turns A&B lamps on
  • Button 2 turns B lamps on only (will turn A off if on)
  • Button 3 disables Occupancy Sensor for 1 hour
  • Button 4 toggles the C lamps

OPTION 2:

  • Button 1 toggles A lamps 
  • Button 2 toggles B lamps 
  • Button 3 disables Occupancy Sensor for 1 hour
  • Button 4 toggles the C lamps

OPTION 3:

  • Button 1 turns A lamps on only (will turn B off if on)
  • Button 2 turns B lamps on only (will turn A lamps off if on)
  • Button 3 disables Occupancy Sensor for 1 hour
  • Button 4 toggles the C lamps

OPTION 4:

  • Button 1 turns A&B lamps on 100%
  • Button 2 turns A&B lamps on 50%
  • Button 3 disables Occupancy Sensor for 1 hour
  • Button 4 toggles the C lamps

 

*NOTES:  A lamps respond to Switch Channel 1,  B lamps respond to Switch Channel 2, C lamps respond to Switch Channel 4. 

When any of the scenes are active, hitting the buttons a second time will turn the corresponding lights off.

Button 3 disables the occupancy sensor by setting the Occupancy time delay to 1 hour and prevents re-triggering of the sensor by movement and will not change the states of the lights.  Hitting button 3 again will revert the occupancy sensor back to the default time delay.

 

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Comments

Powered by Zendesk