Follow

Low Voltage Sensors: Will Sensor Switch Low Voltage Sensors Work With The Lutron PP20 Power Pack?

No, SSI low voltage sensors will not work with the Lutron PP20 power pack.    Although the Lutron part number and functionality are very similar, the signaling between the Lutron PP20 and SSI sensors are not compatible.  

Was this article helpful?
0 out of 0 found this helpful
Have more questions? Submit a request

Comments

  • Avatar
    Matthew Prince

    Be aware that the difference between the Lutron PP20 and SSI PP20 is the Blue LV wire on the Lutron device where SSI PP20 uses a White LV wire to tie in the sensors. Also the Blue wire on the Lutron device is looking for a 24v DC signal where SSI devices will only put out 15v DC signal, not enough to trigger the Lutron PP20.